FireProtect 2 is a next-gen detector designed for residential fire safety. The unique smoke chamber does not require regular cleaning, the dual-spectrum sensor distinguishes smoke from steam, the thermistor quickly reacts to the synthetic materials burning, and sophisticated software minimizes false alarms.
Thought-out design, mounting, and in-app settings make installation straightforward and quick. Everything meets the most modern fire safety standards.
SB - version with sealed batteries giving 10 years of operation.
147.04
€
Without VAT 121.52 €
Payment by Comgate
Need help with a choice?
Patented smoke chamber technology Encouraged by world standards and best practices, Ajax reaches an entirely new level of technology in residential fire safety with FireProtect 2. A unique smoke chamber that is dustproof and impenetrable for insects, a dual-spectrum optical sensor, and a proprietary HazeFlow 2 software algorithm guarantee the speed and accuracy of fire detection — ultimate safety with no stress about false alarms. Impenetrable for dust and insects The smoke chamber is designed with zero possibility of contamination that can affect detection. A unique circulation mechanism provides the optical sensor with an unobstructed field to quickly identify products of combustion in the air. Protects from invisible danger Carbon monoxide (CO) is colorless, odorless, and otherwise imperceptible without a carbon monoxide detector, so poisoning can occur unnoticed. Even low concentrations can be enough to have a negative health impact, especially on those with chronic illnesses, pregnant, the elderly, and young children. High-level exposure can cause permanent damage or even death in a very short period of time. FireProtect 2 warns about a dangerous CO concentration at the level of 50 ppm before even the first signs of poisoning occur. A built-in chemical sensor is responsive to low concentrations and can accurately detect the CO level straight up to 10 years.
Ignores сooking fumes and water steam The smoke chamber is hardwired with a dual-spectrum optical sensor that has blue and infrared LEDs with different wavelengths. It uses the most reliable real-time detection method, directly measuring the microparticle concentration in the air. This technology allows FireProtect 2 to determine the size of the volatile particles inside the chamber and respond only to smoke, ignoring vapour and water steam.Only real threats considered In-depth research on materials combustion resulted in HazeFlow 2 — a smoke detection algorithm developed by Ajax. The algorithm contemporaneously analyses and compares data from the dual-spectrum optical sensor to a specified pattern to define smoke from vapour or steam. The detector instantly raises the alarm when pattern dynamics indicate a real case of fire.Even when it's fire without smoke FireProtect 2 is equipped with two class A1R thermistors to detect smokeless fire threats. They give a significant advantage in detecting a rapid temperature rise when synthetic materials burn, or a fire starts from smoldering. Thermistors are located outside the enclosure to eliminate life-saving detection delays. So FireProtect 2 is ready to detect a fire as fast as possible, even if it starts imperceptibly.
Compatibility
Hub Plus, Hub 2 (2G), Hub 2 (4G), Hub 2 Plus, Hub Hybrid (2G), Hub Hybrid (4G), ReX, ReX 2
Jeweller communication technology
Proprietary wireless technology for transmission of alarms and events. Features: Two-way communication, Protection against device spoofing, Block encryption featuring a floating key, Instant notifications, Remote configuration via the Ajax apps
Maximum effective radiated power (ERP)
up to 20 mW
Radio signal modulation
GFSK
Radio communication range
up to 1,700 m
Encryption of radio communication
All the data stored and transmitted are protected by block encryption with a floating key
Radio frequency hopping
To prevent radio interference and jamming
Sensitive elements
Smoke sensor, heat sensor, CO (carbon monoxide) sensor
Sensitive element
double-spectrum optical sensor
Protection from false alarms
Does not react to water vapor
Patented smoke chamber
Protects the smoke sensor from dust, dirt, and insects
Sensitive element
according to the requirements for Class A1 heat detectors
High temperature alarm
at temperatures above 64°C
Temperature spike alarm
when the temperature rises more than 10°C in 1 minute or less
Carbon monoxide (CO) detection
chemical CO sensor
Alarm if accumulated dose of CO is exceeded
more than 50 ppm (0.005%) — no more than in 90 minutes, more than 100 ppm (0.01%) — no more than in 40 minutes, more than 300 ppm (0.03%) — no more than in 3 minutes
Sensor life
10 years
In-built siren
volume 85 dB at a distance of 3 meters
LED indication
green is a power indication, yellow is an indication of malfunctions, red is an indication of fire alarms
Button on the front panel of the detector
+
Anti-sabotage protection
Tampering alarm, Protection against spoofing, Detection of communication failure
Power supply
2 non-replaceable lithium batteries. 10 years of battery life
Dimensions
124 × 124 × 45 mm
Weight
274.5 g
Operating temperature range
from 0°С to +50°С
Operating humidity
up to 80%
Protection class
IP20